Operational Testing
91
toggle switch)
When a single-phase is TRIPPED/ OPENED, the myPV ClearSky’s PT voltage
reference is still sensing grid voltage as the PT taps are located on the Utility side of
the MV Breakers
The process described above may be repeated for the remaining phases for full
IEEE testing compliance
At any time a single-phase is OPEN, rotating the Selector Mode Switch to
AUTOMATIC will enable protection logic and force a 3-phase TRIP condition
The SPD-TEST button will automatically reset to DISABLED after 50 minutes from
the time it is first enabled
A single-phase that is TRIPPED by pressing and of the A-PHASE, B-PHASE, or C-
PHASE buttons may be CLOSED by simply pressing the same button again (like a
Additional notes on single-phase mode operation: