Protection Relay Settings
34
The myPV ClearSky PLUS routes all OPEN/TRIP and CLOSE commands through the
Protection Relay (SEL-751). The SEL-751 may be interacted with normally though the
push button interface, the SEL AcSELerator software, or via SCADA command. The
SEL-751 does not immediately CLOSE when commanded, instead it coordinates the
CLOSE event with a secondary logic device called the “RVC Controller”.
CLOSE SEQUENCE
1. CLOSE command to SEL-751 (RVC, Local, Software, SCADA, or Reclosing)
2. If ready, SEL-751 signals RVC to start automated switching sequence (maintained
signal)
3. RVC CLOSEs LV Relay Contactor (maintained coil)
4. RVC Controller verifies LV CLOSE via AUX contact.
5. After delay, RVC Controller signals SEL-751 to CLOSE MV Breaker
6. If ready, SEL-751 sends CLOSE command to MV Breaker controller
Automated Inrush Mitigation Switching
Summary of Contents for ClearSky Plus
Page 21: ...Resources 21 ...
Page 22: ...Resources 22 ...
Page 28: ...Design Considerations 28 myPV ClearSky PLUS 25kV Termination Cabinet Door Swing ...
Page 38: ...Receiving 38 Equipment is Wrapped Palletized Typically Equipment Delivery ...
Page 45: ...Receiving 45 Top Fuse Mounting Hardware Three 3 MV Fuses Fully Assembled Installed ...
Page 52: ...Electrical Terminations 52 LV Termination Cabinet ...
Page 56: ...Network Integration 56 ...
Page 64: ...Pre Energization Checks 64 View of Center Switching Cabinet Through Wire Glass Window ...
Page 67: ...Pre Energization Checks 67 View of Three 3 PT Fuses Through Wire Glass Window ...
Page 93: ...Operational Testing 93 Numbered Illustration of Protective Relay Indicators ...
Page 102: ...Spare Parts 102 ...
Page 103: ...Spare Parts 103 ...