14
ELECTRICAL CONNECTIONS (CONT.)
The incoming cable should be hidden.
IMPORTANT:
The shower unit is supplied
with 2 separate sets of connecting
terminal blocks mounted on the shower
back plate so that the shower can be
wired for left or right installations with
minimum effort.
ONLy connect to one of
the terminal blocks.
The diagram below shows the route of the
cable into the shower unit for connection
to the terminal block. (illustrated on left
hand side)
IMPORTANT:
Remove the appropriate
lower cover section to improve access for
mains cable fitting.
Earth
cable to terminal marked
Neutral
cable to terminal marked
N
Live
cable to terminal marked
L
The outer sheath of the supply cable must
be striped back to the minimum length as
illustrated and the earth conductor must
have an earthing sleeve fitted.
IMPORTANT
Ensure that the terminal block screws are fully tightened and that no cable insulation
is trapped under screws. Ensure the cable clamp is used to secure the cable. The
earth continuity conductor of the electrical installation must be effectively connected
to all exposed metal parts of other appliances and services in the room in which the
shower unit is installed to confirm
N
E
Terminal
block
L
KW
RATING
NOMINAL
AT 240V
MINIMUM
RATING OF
ISOLATING
SWITCH
FUSE
RATING
MAX CABLE
RUN
6mm 10mm
7.5
31.25amps
40amps
40amps
29m
48m
8.0
33.33amps
40amps
40amps
27m
44m
8.5
35.41amps
40amps
40amps
23m
38m
9.5
39.58amps
40amps
40amps
21m
32m
10.5
43.75amps
45amps
45amps
18m
30m
!
!
!
!