5 .4 Selecting the Diversion Load
It is critical that the diversion load be sized correctly. If the load is too small, it cannot divert enough
power from the source (wind, hydro, etc). The battery will continue charging and could be overcharged.
If the diversion load is too large, it will draw more current than the rating of the W4B-120C.
CAUTION:
The diversion load must be able to absorb the full power output of the source, but
the load must never exceed the current rating of the W4B-120C wind charger. Otherwise,
the battery can be overcharged and damaged.
5 .5 Capacity
1. When WS-120C connects with 48VDC batteries, it can support 6KW Wind Turbine.
2. When WS-120C connects with 24VDC batteries, it can support 3KW Wind Turbine.
3. When WS-120C connects with 12VDC batteries, it can support 1.5KW Wind Turbine.