USER MANUAL
11
Select one of the 7 standard battery charging algorithms, or select NiCad to determine the
charging of the battery.
The above setting voltage value is in the condition of 12V system. The voltage will be twi-
ce of above values in the 24V system and it will be four times of above values in the 48V
system.
Refer to section 7.0 of the manual for battery charging information.
The 7 standard charging algorithms above are described in section 4.2-standard battery
charging programs.
DIP Switch Number 7 (ON): Auto Equalization;
DIP Switch Number 7 (OFF): Manual Equalization
2 .4 .3 Finish Installation
Inspect for tools and loose wires that may have been left inside the enclosure.
Check the power conductors to make sure they are located in the lower part of the wiring
compartment and will not interfere with the cover and the LCD meter assembly.
NOTE: If the power conductors are bent upwards and touch the LCD meter assembly, pres-
sing the cover down on the wires can damage the meter.
•
Carefully place the cover back on the wind charger and install the one cover screw.
•
Closely observe the system behavior and battery charging for 2 to 4 weeks to confirm
the installation is correct and the system is operating as expected.
DIP Switch Number 4, 5, 6-Battery charging algorithm
DIPSW-4
DIP
SW-5
DIP
SW-6
Bulk
voltage
Float
voltage
Equalize
Voltage
Equali-
ze Time
(hours)
Equalize
Interval
(days)
OFF
OFF
OFF
14.0V
13.4V
None
-
-
OFF
OFF
ON
14.1V
13.4V
14.2V
1
28
OFF
ON
OFF
14.3V
13.4V
14.4V
2
28
OFF
ON
ON
14.4V
13.4V
15.1V
3
28
ON
OFF
OFF
14.6V
13.4V
15.3V
3
28
ON
OFF
ON
14.8V
13.4V
15.3V
3
28
ON
ON
OFF
15.0V
13.4V
15.3V
3
14
ON
ON
ON
16.0V
14.5V
-
-
-