Section 50
00-02-0674
04-16-10
-
26 -
Min value is 1F
Max value is 100F
o
CONFIG_5 (register 43) Absolute maximum temperature before generating an
event
Default is 195F
Min value is 0F
Max value is 2150F
o
CONFIG_6 (register 44) Absolute minimum temperature before generating an
event
Default is 32F
Min value is 0
Max value is 2150F
4. Confirm that the values are written correctly.
NOTE:
Always test Remote operation after programming.
Sensor Event Retry Counter
The sensor event retry counter is located at MODBUS register 20 into each Remotes
MODBUS map. Therefore, the counter for Remote #1 would be located at register 220,
Remote #2 at register 270, etc.
When a sensor event occurs, the Remote transmits this event to the Gateway. If this
transmission was received by the Gateway, then the sensor event retry counter would read 1
(one).
If it took the Remote three times to transmit the event to the Gateway, then the sensor event
retry counter would read 3 (three).
This counter provides the operator with a measure of the system operational integrity when a
sensor event occurs.