Section 50
00-02-0674
04-16-10
-
19 -
MODBUS Register Access
Gateway:
MODBUS Registers 1-199
See the MODBUS map overview for more information (see below).
Remote:
Each Remote is provided with a dedicated range of 50 (fifty) MODBUS registers as outlined
in the table below. Access to a remote is made by adding the MODBUS register you wish
to access to the base address of the remote in question.
For instance, the firmware revision is located at register 6 into each
remote‟s address
space. Therefore, reading the firmware revision requires a read from register:
Remote #1 would read from 206 (200 + 6).
Remote #6 would read from 456 (450 + 6).
Writing to a Remote operates the same way. For instance, Configuration Register 0
(CONFIG_0) is located at register 38. Writing to CONFIG_0 requires writing to:
Remote #1 would write to 238 (200 + 38).
Remote #6 would write to 488 (450 + 38).
Remote 1:
MODBUS Registers 200-249
Remote 2:
MODBUS Registers 250-299
Remote 3:
MODBUS Registers 300-349
Remote 4:
MODBUS Registers 350-399
Remote 5:
MODBUS Registers 400-449
Remote 6:
MODBUS Registers 450-499
Remote 7:
MODBUS Registers 500-549
Remote 8:
MODBUS Registers 550-599
Remote 9:
MODBUS Registers 600-649
Remote 10:
MODBUS Registers 650-699
Remote 10:
MODBUS Registers 700-749
Remote12:
MODBUS Registers 750-799
Remote 13:
MODBUS Registers 800-849
Remote 14:
MODBUS Registers 850-899
Remote 15:
MODBUS Registers 900-949
------------------------------------