Section 50
00-02-0674
04-16-10
-
17 -
3. Initiate Learn Operation at the Remote by pressing and holding the Activation Button
(S301) on the Remote until DS302 flashes two times, then release.
4. Learn Operation Visual Indication
o
Learn Operation Succeeded:
Remote: DS301 will flash rapidly followed by DS302 flashing two times to
confirm success.
Gateway: The COP (MISC) LED will stop flashing rapidly and the FET
LED will illuminate that corresponds to the Remote we just added.
o
Learn Operation Failed:
Remote: DS301 will stay on continuously while DS302 flashes five times
to confirm failure.
Gateway: The COP (MISC) LED may stop flashing as soon as the learn
operation is initiated at the Remote indicating that the Learn Operation
failed part way through the learn process.
Gateway: The COP (MISC) LED may continue to flash indicating that the
Gateway never received the initial communication packet from the
Remote.
5. Learn Operation success can be confirmed via the MODBUS map by viewing the
following MODBUS registers:
o
Register 8 which holds the „Number of Remotes Added‟ will increment each time
a remote is added.
o
Register 15 which holds the „Next Remote to Add‟ will increment each time a
remote is added.
How to Remove a Remote from the Network
1. Ensure the Gateway is powered up.
2. On the Gateway, write a value of 4660 to MODBUS address 40053 to enable MODBUS
writes.
3. On the Gateway, write the remote ID to be removed to MODBUS address 40055 two
times. This will remove the remote from the network.
4. Continue removing any undesired remotes.