MULTICOM 5 PLUS INSTALLER MANUAL
16
User Password
/ Default: user
SMS
1 6
u s e r
This is the access password for serial and
Bluetooth interfaces. This can not be
programmed via PSTN.
PSTN Fault Threshold (Volts)
/ Default: 3
SMS
1 7
0 3
DTMF
* 1 7
0 3
#
Voltage to detect line failure at (3V
default)
Contact ID Retry Delay
/ Default: 15
SMS
1 8
1 5
DTMF
* 1 8
1 5
#
Time delay between Contact ID retries (in
seconds), time is based on the start of
dialling, default 15 seconds.
CID Base message
/ Default: 18095099900
SMS
2 0
X X X X X X X X X X
DTMF
* 2 0
X X X X X X X X X X
#
This is the default base Contact ID
message, refer to the format template
table for individual alarms.
Line Fault Switch Delay
/ Default: 300
SMS
2 5
3 0 0
DTMF
* 2 5
3 0 0
#
Switching delay for the Mode3 Relays on
failure restore (in milliseconds), Default
300mS. This must be very quick, as the
MC5P will connect directly to the
attached panel to take control of the
communications.
Poll Fail Detection Delay
/ Default: 150
SMS
2 6
1 5 0
DTMF
* 2 6
1 5 0
#
This monitors all paths for polling within the
programmed time; this is mapped to the
relays. Default 150 seconds. See option 38
for relay map. See option 39 for enabling
CID notification.
Battery Fault Detection Delay
/ Default: 10
SMS
2 8
1 0
DTMF
* 2 8
1 0
#
Delay before reporting backup battery
fault (minutes). This is also used as AUX trip
for fault relays, see option 38 for relay
map. See options 39 for enabling CID
notification.
AC Fault Detection Delay
/ Default: 15
SMS
2 9
1 5
DTMF
* 2 9
1 5
#
Delay before reporting AC failure (in
minutes) Default 15 minutes. This is
mapped to the fault relays, see 38. See
options 39 for enabling CID notification.
Zone enable / Disable
/ Default: 0000
ZONE
4
3
2
1
SMS
3 0
0 0 0 0
DTMF
* 3 0
0 0 0 0
#
To disable zones set to zero, to enable set
to one. Default is all zones disabled. Zones
are all 24 hour zones. These are mapped
to fault relays by option 38.