MULTICOM 5 PLUS INSTALLER MANUAL
15
Programming Options
Account Code
/ Default: Auto Detect
SMS
0 1 9 9 9 8
DTMF
* 0 1 9 9 9 8 #
Contact ID account code used by the 5
Plus Note: Panels that report multiple
account codes may be changed from the
code that was initially taken from the
alarm panel. This option can be changed
during the commissioning procedure with
the Suretek Activations Centre.
Primary CMS Number
/ Default: Blank
SMS
0 2
1 3 4 5 X X X X
DTMF
* 0 2
1 3 4 5 X X X X
#
Central Monitoring Station Phone number
for when the Multicom communicates via
GSM or PSTN (Max 19 digits) eg. 13451111
or 1300111222
PBX Prefix
/ Default: Blank
SMS
1 9
X X X X X
DTMF
* 1 9
X X X X X
#
Optional number for getting an external
line out via PSTN (not GSM) (Max digits is 5)
Secondary CMS Number
/ Default: Blank
SMS
3 7
1 3 4 5 X X X X
DTMF
* 3 7
1 3 4 5 X X X X
#
Program this to the same backup phone
number in the attached panel. This is only
used to allow ComWatch to detect if the
panel is attempting to dial the backup
number, the Multicom will not dial this
number.
ComWatch Mode Count
/ Default: 3
SMS
0 5
3
DTMF
* 0 5
3
#
How many attempts the attached panel
has to correctly deliver a Contact ID
message to the monitoring station before
the Multicom takes priority. Program to 0 to
disable.
E.g the panel dials 3 times and no
handshake or kiss off tones are heard, the
Multicom will take control of the alarm
delivery path.
ComWatch Mode Bypass Time
/ Default: 24
SMS
1 2
2 4
DTMF
* 1 2
2 4
#
This is the time in hours that the Multicom
will hold priority after ComWatch detects
that alarms could not be delivered via
PSTN/GSM.
Multicom/PSTN Priority
/ Default: 1
SMS
1 1
1
DTMF
* 1 1
1
#
0
= Multicom is the priority line for the
attached panel,
1
= PSTN is the primary
line for the attached alarm panel
.
External Panel Programming Timer
/
Default: Blank
SMS
1 3
X X
DTMF
* 1 3
X X
#
Program this in minutes. This feature allows
bypassing of the Multicom for a
programmed period, so that you can
program an attached panel.