1.4550.136 – B - Temperature derating active
Yellow alarm. Initiated by ProAct B-Bank.
Cause
Corrective action
The internal temperature is
higher than the limit.
1. Check room temperature. Restart ProAct.
2. Restart ProAct.
1.4550.137 – B - Temperature above 120 °C
Red alarm. Initiated by ProAct B-Bank.
Cause
Corrective action
The internal temperature is
higher than the limit.
1. Check room temperature. Restart ProAct.
2. Restart ProAct.
1.4550.138 – B - Loss of Position Demand
Red alarm. Initiated by ProAct B-Bank.
Cause
Corrective action
Position demand is missing or
out of range
1. Check setting.
2. Check cabling.
1.4550.139 – B - Demand Tracking Fault
Yellow alarm. Initiated by ProAct B-Bank.
Cause
Corrective action
ProAct setting is not correct.
u
Check setting.
1.4550.140 – B - Analog Position Demand Failed
Yellow alarm. Initiated by ProAct B-Bank.
Cause
Corrective action
ProAct setting is not correct.
u
Check setting.
1.4550.141 – B - PWM Position Demand Failed
Yellow alarm. Initiated by ProAct B-Bank.
Cause
Corrective action
ProAct setting is not correct.
u
Check setting.
1.4550.142 – B - CAN Position Demand Failed
Red alarm. Initiated by ProAct B-Bank.
Cause
Corrective action
Position demand not received or
received too late
u
Check cabling and setting.