4.3 Engine start in manual operation (trials)
Preconditions
☑ Generator is not connected to network.
☑ External start interlock is not activated.
DANGER
Unguarded rotating and moving engine components.
Risk of serious injury – danger to life!
• Before barring or starting the engine, make sure that nobody is in the danger zone.
WARNING
Engine noise above 85 dB (A).
Risk of damage to hearing!
• Wear ear protectors.
Preparation
Item
Task
Operating mode selector
switch (if provided)
Change to manual mode.
Starting the engine
Item
Task
Switchgear cabinet, control
panel etc. (depending on
manufacturer)
Press start button.
• Automatic starting sequence is performed;
• Engine speed display instrument indicates increasing speed;
• After the starting sequence is completed, engine is running at rated
speed.
Connecting the generator to network, running the engine to reach operating
temperature
Item
Task
Switchgear cabinet, control
panel etc. (depending on
manufacturer)
Close the generator circuit breaker.
Engine
Apply full load only after engine has reached operating temperature (cool‐
ant temperature approx. 60 °C).
70 | Operation | MS15022/02E 2012-04