background image

same size as the pump inlet or sized 

based on reasonable fluid friction 

losses.

A foot valve is recommended when 

lifting fluid from a sump.  This will 

save wear and tear on any pump, 

even those equipped with self-prim-

ing equipment.

A suction strainer is recommended 

immediately ahead of the pump on 

any newly constructed system.  This 

is advisable due to the probability 

that foreign material large enough 

to damage pump clearances may 

remain even though the piping has 

been flushed.

Valves in the outlet piping of a regen-

erative turbine pump should always 

be open as far as possible when the 

pump is started.  This will reduce 

the start-up load on the pump and 

motor.  Never start the pump with the 

discharge valve closed.

Inlet valving should be open when 

starting any pumping system.  With-

out some fluid in the pump, it can gall 

and lock up impellers.  Violent pump 

failure will result from continued 

operation with the inlet or discharge 

valve closed.

1D4 Priming

Regardless of whether self-priming 

equipment is used or not, always fill 

the pump and vent it of air for best 

seal and pump life.  Under most 

circumstances, regenerative turbine 

pumps can be made to self-prime as 

long as a small amount of fluid can 

be recirculated through the impeller 

and the fluid doesn’t heat up notice

-

ably.

1D5 NPSH (Net Positive Suction 

Head)

The NPSH required varies with every 

size and capacity of pump and gener-

ally comes into consideration when 

the fluid being pumped approaches 

its vapor pressure or boiling point.  

The NPSH requirements of regen-

erative turbine pumps are different 

from centrifugal pumps in that there 

is no single specification for a given 

unit.  The pump curve of head vs. 

capacity will vary according to the 

NPSH available, but does not have a 

minimum requirement like a centrifu-

gal.  The performance of each unit at 

a given NPSH can be obtained from 

the performance curves or from your 

MTH representative.  Understanding 

this, we can say that there will be a 

minimum NPSH required to obtain a 

specific performance from a unit ac

-

cording to its NPSH curves. 

If the NPSH Available (NPSHA) is not 

equal to or greater than that required 

by the pump (NPSHR), it must be in-

creased or a different pump selected.  

The usual method for increasing 

NPSH is to raise the static head on 

the pump inlet, (H

s

) by raising the 

source tank or lowering the pump.

By definition, NPSH means: “Net 

Positive Suction Head” above the 

vapor pressure of the pumped 

liquid available at the centerline 

of the pump.  It should always be 

given in feet of pumped liquid.  The 

NPSH is actually a measurement 

of the amount of energy available 

in the pumped liquid to produce the 

required absolute entrance velocity in 

the pump.  If a pump requires more 

energy (or NPSH) than is available at 

a given capacity, the pressure at the 

inlet will fall below the vapor pres-

sure of the pumped liquid, and loss of 

performance will result.  The NPSH 

available may be calculated using the 

following equation.

NPSHA = 2.31(             )+ H

s

- H

f

P

s

 = Pressure in the suction vessel 

in PSIA.

P

vp

 = Vapor pressure of the pumped 

fluid in PSIA.

H

s

 = Static height of the pumped fluid 

above (+) or below (-) the centerline 

of the pump.

H

f

 = All friction losses from the vessel 

to the pump including pipe, valve, 

and suction strainer friction.

For boiling liquids, P

s

 and P

vp

 are 

equal, this term then becomes zero, 

and can then be omitted from the 

equation.  Please refer to the Hy-

draulic Institute Standards and fluid 

friction loss tables for more informa-

tion on this subject.

1D6 Noise

While not generally considered 

especially noisy, regenerative turbine 

pumps often produce a high pitched 

whine that increases in intensity as 

the differential pressure produced 

in the pump increases.  While high 

frequency sound is attenuated more 

easily than lower frequencies, piping 

structures and the fluids in them 

readily transmit and even amplify 

noise.  Motors, bearings, and other 

rotating components add to noise 

and sometimes create objectionable 

harmonics.

Careful pump installation can con-

tribute to noise reduction.  Proper 

alignment of the pump and driver is 

essential.

Adequate supports for the inlet and 

discharge piping are equally impor-

tant.  A degree of noise reduction 

may be obtained when the pump-

ing unit is supported free of building 

structures by the use of vibration 

isolators, flexible piping and conduit 

connections.  Elastomer type cou-

plings are the best choice to separate 

motor noises from the fluid and piping 

structure.

1D7 Freezing

When ambient temperatures drop be-

low the freezing point of the fluid in a 

pump, consideration should be given 

to heating, insulating, or draining the 

pump.  If you choose draining, and 

it will only be for a short period, first 

remove the drain plugs and drain the 

lines to and from the pump.  Carefully 

blow out the pump with compressed 

air to clear all internal cavities of fluid.  

DO NOT use automotive anti-freeze 

in pumps as the silicates present in 

these fluids cause damage to me

-

chanical seals.

1E Recommended Spare Parts

FOR CRITICAL SERVICES - a 

duplex installation, with two identical 

pumping units in parallel, is the safest 

and many times the most cost effec-

tive choice.

FOR IMPORTANT SERVICES - a 

standby pump, ready for installation 

is advised.

P

s

 - P

vp

sp. gr.

Page 503

Summary of Contents for P31 Series

Page 1: ...P31 SERIES Section P31 Page 501 Dated October 2010 97 5006 01 588 Pump Manual HORIZONTAL CLOSE COUPLED ADJUSTABLE PERFORMANCE INTEGRAL RELIEF VALVE OPTION...

Page 2: ...the shaft Apply ing torque to the motor fan blades is not recommended If the impeller does not break loose immediately fill the pump with a process compatible fluid and try again in a few hours If thi...

Page 3: ...in feet of pumped liquid The NPSH is actually a measurement of the amount of energy available in the pumped liquid to produce the required absolute entrance velocity in the pump If a pump requires mo...

Page 4: ...l the components required for servic ing plus shaft sleeve and drive keys should be obtained A factory re build should be considered whenever your disassembly indicates rebuilding is necessary as this...

Page 5: ...foundation until it has been properly aligned The foundation must be a perma nent rigid installation of concrete or other material of sufficient mass to absorb all normal vibrations Locate the founda...

Page 6: ...ant to be aware of and follow the appropriate local and na tional electrical codes Do not make wiring alterations that can affect motor rotation without reconfirming correct rotation Select starters a...

Page 7: ...uction lines are desirable to minimize priming time Usingtheself primingequipment itis only necessary to 1 Open the plugs in both the inlet and discharge chambers 2 Pour fluid in one until both are fu...

Page 8: ...able consideration should be given to switching to a sealless leak free design Most MTH pumps are available in a sealless canned motor design See the SP31 4B Flushing Lines External Flushing lines are...

Page 9: ...x 6 long 8 Thin blade screwdriver 9 Cealube G P 80 or glycol base lubricant compatible with the pro cess fluid and O ring elastomers DO NOT use petroleum prod ucts To disassemble the pump Refer to Fig...

Page 10: ...rances between the casing and impeller probably exceed the maximum allow able The P31 features an adjustable casing that may allow return to like new performance See Section 5D for more information If...

Page 11: ...ng careful not to damage the seat or the rotating element 4 Compress and hold the seal spring slightly below the snap ring groove and install the snap ring 4 Make sure the snap ring is locked firmly i...

Page 12: ...al attention should be given to the seal area where the motor shaft enters the motor bracket 6 Under pressure the impeller will find its hydraulic balance 7 Using an amprobe or similar de vice check f...

Page 13: ...onents 6 Air pockets in the suction piping Operating the system at maximum flow conditions will usually clear the lines Evacuate the system with a vacuum pump if necessary 7 Suction lines strainer or...

Page 14: ...clear ances rusty Follow installation instructions for loosening the pump Foreign material in pump Flush out Disassemble if flushing is not successful 3 Pump leaks Seal or O rings are usually the pro...

Page 15: ...ump was purchased or supplied Complete details on what is wrong with the pump must be provided along with information on the system in which it is installed Refer to the MTH Pumps Limited Warranty sta...

Page 16: ...marked with the Return Goods Authorization RGA number provided by MTH and shipped freight prepaid and allowed F O B the MTH factory at Plano Illinois USA MTH may in its sole discretion deny any warra...

Reviews: