OPERATING AND MAINTENANCE MANUAL

Chapter 2 - Safety

TAEevo Tech MINI 02÷10

7

The data in this manual are not binding and they can be modified by the manufacturer without notice. 

Reproduction of this manual is strictly prohibited

EN

ENGLISH

When mains power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised 
if any work must be carried out on the electrical system.
Do not open the electrical equipment guard panels while the circuit is energized. Operations that require intervention with the 
electrical circuit energized must be performed only by qualified personnel using appropriate equipment and wearing apparel 
and devices designed to protect against electrical hazards.

2 . 6

D i s p o s a l

If the product is scrapped, it must be disposed of in accordance with the environmental protection legislation in force in the 
country of use. The unit may include all or some of the materials listed below:

Refrigerant fluid R134a/R410A

Copper parts

Aluminium parts

Carbon Steel parts

Stainless Steel parts

PVC  parts

CFC-free synthetic insulating material

Polystyrene parts

Polyester oil

Brass

2 . 7

M a i n t e n a n c e   p r e c a u t i o n s

ATTENTION

 

When it is necessary to discharge waste material do not pollute water pipelines, groundwater or watercourses.

Avoid the combustion of materials that could produce fumes that are toxic and harmful when released into the atmosphere.
Protect the environment by using only approved methods of disposal.

Keep a written record of all work carried out on the unit and the auxiliary equipment. The frequency and the nature of the 
work required over a period can reveal adverse operating conditions that should be corrected.

ATTENTION

 

Use only the refrigerant specified on the data plate of the unit.

Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit, with all 
accessories and safety devices, is kept in good working order. The accuracy of pressure and temperature gauges must be 
regularly checked. If values are discovered that exceed the permissible tolerances, the gauges must be replaced.

ATTENTION

 

Do not perform welding procedures or other operations that can produce heat in the vicinity of elements containing oil

or flammable liquids. Systems which may contain oil or flammable liquids must be completely purged and cleaned, e.g. with
steam, before carrying out such operations.

Components in the vicinity must be protected with non-inflammable material and, if the operation is to be performed close to 
parts of the lubrication system or in the vicinity of components that may contain oil or inflammable liquids, the system must 
first be purged.
Never use an open flame as a light source to inspect parts of the unit.
For all units establish a suitable time interval for cleaning procedures.

ATTENTION

 

If replacement parts are needed use only original spares.

Take care not to damage pressure limiting devices.
All guards must be refitted after carrying out repair or maintenance work.

ATTENTION

 

Check the direction of rotation of the motors (the pump, if installed) when starting the unit for the first time and after

work has been performed on the electrical connections or on the power supply sectioning device.

Summary of Contents for TAEevo Tech MINI

Page 1: ...T A E e v o T e c h M I N I WATER CHILLERS OPERATING AND MAINTENANCE MANUAL TAEevo Tech MINI 02 10 38178801054 Original instructions in Italian language...

Page 2: ...unit is on the display shows the regulator probe value If the unit is in standby mode the display shows 0 1 2 Switch on from digital input NOTE Refer to the wiring diagram for connection of the digit...

Page 3: ...operation 6 2 6 Disposal 7 2 7 Maintenance precautions 7 2 8 Refrigerant gases 8 2 8 1 Refrigerants safety datasheet 8 Chapter 3 TECHNICAL DATA 11 3 1 Declaration of conformity 12 3 2 Data for standar...

Page 4: ...from the keypad 22 7 3 2 Switch on from digital input 22 7 4 Setpoint 22 7 4 1 Displaying the setpoint 22 7 4 2 Modifying the setpoint 22 7 5 Maximum and minimum temperature 22 7 6 Modifying the value...

Page 5: ...ffixed to the unit and also in the dimensional drawings and refrigerant circuit diagrams The meaning of each symbol is indicated below 1 1 H o w t o i n t e r p r e t t h e m o d e l ATTENTION This ma...

Page 6: ...ntenance of the unit and auxiliary equipment can be dangerous and can cause serious or fatal accidents We cannot anticipate every possible circumstance which might constitute a potential hazard The wa...

Page 7: ...e unit empty and in the basic configuration The manufacturer does not supply load spreaders lifting straps or hooks with the unit NOTE Weight values are guideline with the water circuit empty The valu...

Page 8: ...carried out on the unit and the auxiliary equipment The frequency and the nature of the work required over a period can reveal adverse operating conditions that should be corrected ATTENTION Use only...

Page 9: ...heavily contaminated refrigerant system e g after a refrigerant compressor burnout a qualified refrigeration engineer must be consulted to carry out the task The manufacturer s instructions and local...

Page 10: ...Local effects Concentrations substantially above 1000 ppm v v can cause narcotic effects Inhalation of products in decomposition can lead to respiratory difficulty pulmonary oedema Long term toxicity...

Page 11: ...ne measures Do not smoke PHYSICAL AND CHEMICAL PROPERTIES Colour Colourless Odour Faint Boiling point 52 8 C at atmospheric pressure Flash point Non flammable Relative density 1 08 kg l at 25 C Solubi...

Page 12: ...REFRIGERANT Refrigerant fluid in the unit REFRIGERANT QUANTITY Quantity of refrigerant fluid contained in the unit MAX REFRIG PRESS Refrigerant circuit design pressure MAX REFRIG TEMP Refrigerant circ...

Page 13: ...s final test f Directives and standards g Officer responsible for technical file h Technical supervisor personal data Model TAEevo Tech MINI 02 03 05 08 10 Tank capacity water volume litres 15 15 15...

Page 14: ...strictly prohibited EN ENGLISH Available head TAEevo Tech MINI 02 03 Available head TAEevo Tech MINI 05 10 NOTE The pump must never run dry 100 150 200 250 300 350 400 0 1 0 2 0 2 0 3 0 3 0 4 0 4 0 5...

Page 15: ...3 2 FT global Test conditions Noise levels refer to operation of the unit at full load in nominal conditions Sound pressure level in hemispherical irradiation conditions at a distance of 1 m 3 2 FT fr...

Page 16: ...5 Evaporator The evaporator is of the finned core type water flows in contact with the finned surface at velocities such as to ensure low pressure drops while the refrigerant flows through the tubes...

Page 17: ...d exclusively to protect the unit in the event of inappropriate closing of the shut off valves The manufacturer advises strongly against operation of the by pass for continuous cycles or lengthy perio...

Page 18: ...e room temperature 3 The ambient air must be clean avoid sea ambients brackish air and not contain flammable gas or corrosive solvents 4 The minimum and maximum working ambient temperature are specifi...

Page 19: ...quantity of antifreeze solution 5 4 L i m i t o p e r a t i n g c o n d i t i o n s 1 For temperatures below 5 C use antifreeze solutions see 5 3 Freeze protection 5 5 P l u m b i n g c o n n e c t i...

Page 20: ...tact in compliance with the prescriptions of IEC 364 by means of a residual current device the nominal trip current of which should normally be set to 0 03 A 3 Make sure the level of protection agains...

Page 21: ...ly voltage is correct 6 Turn the machine main switch ON TAEevo Tech MINI 08 10 7 The Electronic Control Unit switches on 8 The unit is ready to start If with the first start up there is a high ambient...

Page 22: ...nations LED MODE MEANING On C Flashing Parameter menu On Compressor running Flashing Minimum OFF time active Flashing Alarm active On Pump running Key Function Displays or modifies held down for 3 the...

Page 23: ...e unit by closing the digital input contact the unit switches on it switches to standby OFF if it is opened The off command from keypad or digital input always overrides the on command If the unit is...

Page 24: ...sh 4 Edit it with the and keys 5 Press to save the new value and move on to the next parameter To quit Press with a parameter displayed or wait 15s NOTE The new value is saved even if the user quits t...

Page 25: ...turns red to indicate its presence 7 1 1 P a r a m e t e r l i s t Every parameter has a corresponding access level U user level ATTENTION Changing the default parameters may prevent the unit from fun...

Page 26: ...r the compressor and people within the immediate vicinity It is of manual reset type It opens the power circuit of the compressor and of the fan see wiring diagram When the discharge pressure of the r...

Page 27: ...urn it off when there is no thermal load as it turns off automatically when the preset water temperature has been reached 9 2 M a i n t e n a n c e ATTENTION Before proceeding with the maintenance of...

Page 28: ...election of the unit Check that the ambient temperature is lower than the value used for selecting the unit Check that the environment is well ventilated Clean the water filter The water filter should...

Page 29: ...1 See A1 1 low evaporation pressure Get a technician to check for leaks and eliminate them Fill the plant B Probe BT1 faulty B1 Probe faulty or parameters out of range B1 1 Message P1 appears Check o...

Page 30: ...e A1 E6 1 Water outlet temperature too high refrigerant compressor stops Restore the thermal load to within the preset limits Press the reset button on the cap of the pressure switch F Compressor prot...

Page 31: ...d dAO K Low temperature alarm K1 The alarm delay is too short or the alarm threshold too low K1 1 LA low temperature alarm displayed See Ch 7 5 Maximum and minimum temperature Verify parameters ALL L...

Page 32: ...sk of high pressure fluid ejection from pipelines in cooling circuit due to design pressure values being exceeded Contatto di parti del corpo con gas frigorigeno o residui di tubazione del circuito fr...

Page 33: ...bstances handled used produced or offloaded from the machine and materials used to construct the machine fire or explosion Risk of fire or explosion Install the system in an environment fitted with ad...

Page 34: ...chine instability caused by vibrations Hazards on contact with operating fluids risk of pollution due to dispersion of fluids into the environment Strictly observe all manual instructions Chapter 2 Sa...

Page 35: ...f the manual 32 Hazards generated by absence of and or position of measures instruments influencing safety disconnection of power sources Contact with live parts contact with high pressure fluids or g...

Page 36: ......

Reviews: