A l a r m s
7.10.1 Alarm messages
When the unit is on, an alarm icon flashes
and the alarm message appears. The possible alarm messages are listed below:
NOTE
The alarm relay switches status for all alarms.
7.10.2 Alarm relay
The Electronic Control Unit has an alarm signalling relay. Its contact is closed during normal operation and is opened in the
case of an alarm or a power blackout.
Refer to the wiring diagram for the relative connections.
In TAEevo Tech MINI 08-10 models a green light remains on to indicate that there are no alarms in the unit.
If an alarm occurs, the light turns red to indicate its presence.
7 . 1 1
P a r a m e t e r l i s t
Every parameter has a corresponding access level:
U
= user level
ATTENTION
Changing the default parameters may prevent the unit from functioning correctly.
Message
Cause
Outputs
Compr.
Pump
P1
Thermostatic control probe failure
OFF
ON
P2
Room temperature probe failure
OFF
ON
HA
Thermostatic control probe high temperature alarm
ON
ON
LA
Thermostatic control probe low temperature alarm
ON
ON
CA
High pressure switch alarm
OFF
ON
Parameter
Level
Description
Range
Default
settings
SEt
U
Setpoint
LS - US
7
Hy
U
Compressor control hysteresis
(0,1°C÷25,5°C)
(0°F÷45°F)
4
LS
U
Minimum setpoint
(-55,0°C÷SET)
(-67°F÷SET)
5
rES
U
Resolution (per °C): decimal, integer
dE – in
dE
ALU
U
Thermostatic control high temperature alarm setpoint
0,0÷50,0°C rel.
or ALL÷150°C
(302°F)
40
ALL
U
Thermostatic control low temperature alarm setpoint
0.0÷50°C rel.
or -55°C
(-67°F)÷ALU;
4
dP1
U
Thermostatic control temperature value
read-only
(probe value)
--
dP2
U
Room temperature probe temperature value
read-only
(probe value)
--