TECHNICAL MANUAL
Chapter 21
- Double setpoint kit (optional accessory)
NGSi 05÷15
53
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited
The second setpoint is higher than the first setpoint in summer and lower in winter:
•
in summer: T2 >= T
•
in winter: T2 <= T
2 1 . 7
S w i t c h i n g f u n c t i o n s
Switching sequence from normal setpoint to second setpoint:
1. working setpoint change
2.
in summer:
3-way valve only switches when the second setpoint – 5°C has been reached
in winter:
3-way valve only switches when the second se 5°C has been reached
(switching always takes place 5 min after the setpoint change)
Switching sequence from second setpoint to normal setpoint:
1. 3-way valve switches
2. working setpoint changes after a parameter-controlled time equal to opening of the three-way valve (default b04=30s from
maintenance menu)
2 1 . 8
E l e c t r i c a l w i r i n g d i a g r a m
In these diagrams, the domestic hot water tank, system, floor side or fancoil side is the line to which the valve must switch when the relative
connection receives power.
21.8.1
Wiring diagram, configuration without external relay
3-WAY VALVE
DOMESTIC HOT WATER
3-WAY VALVE
DOUBLE SETPOINT
Connection for valve with 3-point power supply only, system side
Domestic hot water tank side
Fancoil side
Connection for valve with 3-point power supply only
floor side
NC2-N2 connection for fan coil consent
Maximum permitted resistive load: 5 A
Maximum permitted inductive load: 1 A
Remote control
serial
Double humidity switch for
NC contact setpoint
Auxiliary heater
220V SA
Sensor
domestic hot water
Summer/Winter
On/Off
remote
Remote c humidity
switch power supply