TECHNICAL MANUAL
Chapter 14
- Electrical data of unit and control devices
NGSi 05÷15
42
ENGLISH
EN
The data in this manual are not binding and they can be modified by the manufacturer without notice.
Reproduction of this manual is strictly prohibited
Performance figures relate to the following conditions:
(1) Cooling: external air temperature 35°C; intake/outlet water temperature 12/7°C.
(2) Cooling: external air temperature 35°C; intake/outlet water temperature 23/18°C.
(3) Heating: external air temperature 7°C d.b. 6°C w.b.; intake/outlet water temperature 40/45°C.
(4) Heating: external air temperature 7°C d.b. 6°C w.b.; intake/outlet water temperature 30/35°C.
(5) Sound level power: determined based on the measurements carried out in accordance with ISO 3744.
(6) Sound pressure at 1 m obtained in free field over a reflecting plane. Tolerance values ± 2 dB. Sound levels refer to the unit under
maximum operating conditions. The data refer to the operating conditions with outside air temp 35°C, water temp. 7/12°C.
NOTE
The stated performance data are guideline and may be subject to variation.
Furthermore, the yields stated in points (1), (2), (3) and (4) are to be understood referring to the instantaneous power according to EN
14511.
C
HAPTER
14
E
LECTRICAL
DATA
OF
UNIT
AND
CONTROL
DEVICES
* For sizes 05, 07 and 10
** For size 15
NOTE
Electrical data are subject to variation due to updates. Therefore, users should always refer to the technical data sticker on the unit’s right
hand side panel.
C
HAPTER
15
H
EAT
PUMP
WORKING
HEADS
Blow are shown the head-flow rate curves net of hydronic kit pressure drop. Each curve shows the optimal operating point under the
conditions specified at the peak (4) of Chapter 13 “Technical data”.
The system must be designed in a manner which guarantees the nominal flow rates for the duty points specified below.
1 5 . 1
M o d . N G S i 0 5
WARNING:
The minimum temperature allowed for the unit storage is 5°C.
Unit power supply
V/~/Hz
230/1/50 *
400/3+N+PE/50
**
Remote control circuit
V/~/Hz
12/1/50
On-board control circuit
V/~/Hz
12/1/50
Fan power supply
V/~/Hz
230/1/50
0
10
20
30
40
50
60
70
0,6
0,8
1,0
1,2
1,4
1,6
Water flow rate [m3/h]
Work head [kPa]
Flow rate [m3/h]