24
FlameGard 5 MSIR HART
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm Relay Status: 1 = Latched, 0 = Unlatched
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1 - 15
Undefined
16 Error
Write
Protect
Mode
17 - 127
Undefined
10.35
Command #162: Read Alarm Relay Latched Status
Read the Remote Alarm Test Mode. A value of 0 indicates normal mode. A value of 1 indicates that the unit is
in alarm test mode.
Request Data Bytes
Byte
Format
Description
0 N/A
N/A
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm Relay Status: 1 = Latched, 0 = Unlatched
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
10.36
Command #163: Set Alarm Relay De-Energized/Energized Status
This sets the alarm relay status to be either De-Energized or Energized. If the DIP override flag is set, then the
command will return an ACCESS RESTRICTED code.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm Relay Status: 1 = Energized, 0 = De-Energized
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm Relay Status: 1 = Energized, 0 = De-Energized