29
FlameGard 5 MSIR HART
11.0
Tables
11.1
FlameGard 5 MSIR – Device Specific Commands Summary
The following Table 4 is a summary of the FlameGard 5 MSIR Device Specific Commands. The Reg values in
the Meaning Column denote the corresponding MODBUS Register.
Table 4: FlameGard 5 MSIR – Device Specific Commands
Command
Number
Byte Number
Meaning
Command 128
Read DIP Switch Override Reg 0x07
Command 129
Write DIP Switch Override Reg 0x07
Command 130
Read DIP Switch Settings Register 0x46
Command 131
Read Unit Options Reg 0x08
Command 132
Write Unit Options Register 0x08
Command 133 0
Read COPM Fault Status Reg 0x06
Command 133 1
COPM Counts sensor 1 Reg 0x0D
Command 133 2
COPM Counts sensor 2 Reg 0x0E
Command 133 3
COPM Counts sensor 3 Reg 0x0F
Command 133 4
COPM Counts sensor 4 Reg 0x10
Command 134
Clear COPM Faults Reg 0x13
Command 135
Remote Alarm Reset Reg 0x11
Command 136
Remote Alarm Test Reg 0x012
Command 137
Read Sensor Temperature Reg 0x14
Command 138
Set/Reset Test Lamp Test Mode Reg 0x5A
Command 139
Read Test Lamp Test Mode Reg 0x5A
Command 140
Read Alarm Delay Reg 0x5B
Command 141
Set Alarm Delay Reg 0x5B
Command 142
Test Lamp Time Stamp Reg 0x6A, 0x6B, 0x6C
Command 143
Read Event Logging Counters: Reg 0xA8, 0xB0,
0xB8, 0xC0
Command 144
Clear Event Logging Counters Reg 0xC1
Command 145
Read Warning Event Log Register
Command 146
Read Alarm Event Log Event Register
Command 147
Read Fault Event Log Register