25
FlameGard 5 MSIR HART
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1 - 15
Undefined
16 Error
Access
Restricted
17 - 127
Undefined
10.37
Command #164: Read Alarm Relay De-Energized/Energized Status
This reads the Energized/De-Energized status of the alarm relay.
Request Data Bytes
Byte
Format
Description
0 N/A
N/A
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm Relay Status: 1 = Energized, 0 = De-Energized
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
10.38
Command #165: Set Sensitivity Level
This sets the unit sensitivity. It may have the values of high, medium, or low. If the DIP override flag is set, then
the command will return an ACCESS RESTRICTED code.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
Unit Sensitivity Level: 0 = High, 1 = Medium, 2 = Low
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Unit Sensitivity Level: 0 = High, 1 = Medium, 2 = Low