21
FlameGard 5 MSIR HART
10.28
Command #155: Read Event Log Index
Read the Event Log Index to a specified value. This index is used by commands 145, 146, 147, & 148 to
retrieve the event information stored in the instrument. The events are accumulated automatically by the
instrument. The most recent event to have occurred is event #0. The next most recent event to have occurred is
event # 1. The least recent event is event # 9.
Request Data Bytes
Byte
Format
Description
0 N/A
N/A
Response Data Bytes
Byte
Format
Description
0 Unsigned-8 Event
Index
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
10.29
Command #156: Read Remote Alarm Test Mode
Read the Remote Alarm Test Mode. A value of 0 indicates normal mode. A value of 1 indicates that the unit is
in alarm test mode.
Request Data Bytes
Byte
Format
Description
0 N/A
N/A
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Remote Alarm Test Mode
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined