20
FlameGard 5 MSIR HART
10.26
Command #153: Read Power Cycle Flag
Read the Power cycle flag. This flag is set equal to one whenever the power is cycled to the unit. When the
clock is set via either by command number 149 or 151, this flag is reset to zero.
Request Data Bytes
Byte
Format
Description
0 N/A
N/A
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Power Cycled Flag Value
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
10.27
Command #154: Set Event Log Index
Set the Event Log Index to a specified value. This index is used by commands 145, 146, 147, & 148 to retrieve
the event information stored in the instrument. The events are accumulated automatically by the instrument.
The most recent event to have occurred is event #0. The next most recent event to have occurred is event # 1.
The least recent event is event # 9.
Request Data Bytes
Byte
Format
Description
0 Unsigned-8 Event
Index
Response Data Bytes
Byte
Format
Description
0 Unsigned-8 Event
Index
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined