AREA
Tells where hazards
may occur.
HAZARD
Tells what the hazard is.
SAFEGUARDS
Tells how to avoid the hazard.
Improper or inadequate
operation and maintenance
procedures will cause a
fire hazard.
Protection against inadvertent
arcing that is capable of
causing fire or explosion is lost
if any safety interlocks are
disabled during operation.
Frequent Power Supply or
Controller shutdown indicates
a problem in the system
requiring correction.
Electrostatic arcing must be prevented. Safe sparking
distance must be maintained between the parts being
coated and the applicator. A distance of 1 inch for
every 10KV of output voltage is required at all times.
Unless specifically approved for use in hazardous
locations, all electrical equipment must be located
outside
Class II, Division 1 or 2 hazardous, zone 21
or zone 22 areas.
Test only in areas free of flammable or combustible
materials.
The current overload sensitivity (if equipped)
MUST be set as described in the corresponding
section of the equipment manual. Protection against
inadvertent arcing that is capable of causing fire
or explosion is lost if the current overload sensitivity
is not properly set. Frequent power supply
shutdown indicates a problem in the system which
requires correction.
Always turn the control panel power off prior to
flushing, cleaning, or working on spray system
equipment.
Before turning high voltage on, make sure no objects
are within the safe sparking distance.
Ensure that the control panel is interlocked with the
ventilation system and conveyor in accordance with
NFPA-33, EN 50177, EN 50050-2.
Have fire extinguishing equipment readily available
and tested periodically.
Improper operation or
maintenance may create
a hazard.
Personnel must be properly
trained in the use of this
equipment.
Personnel must be given training in accordance
with the requirements of NFPA-33.
Instructions and safety precautions must be read
and understood prior to using this equipment.
Comply with appropriate local, state, and national
codes governing ventilation, fire protection,
operation maintenance, and housekeeping.
Reference OSHA, NFPA-33, EN Norms and your
insurance company requirements.
General Use and
Maintenance
Spray Area
Explosion Hazard
PA-18-02-R0 (08/2018)
7 / 52
www.carlisleft.com
SAFETY
EN