6 Functions and settings
Maschinenfabrik Reinhausen 2014
79
2374092/04 EN
TAPCON® 260
Setting Z compensation
This parameter sets the voltage increase ∆V previously calculated.
If you do not want to use Z compensation, you have to set the value 0.0 %.
To set the Z compensation, proceed as follows:
1.
>
Parameter >
Compensation > Press
until the de-
sired parameter is displayed.
ð
Z compensation.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The Z compensation is set.
Setting the Z compensation limit value
You can use this parameter to define the maximum permissible voltage in-
crease to avoid excess voltage on the transformer.
If you do not want to use a limit value, you have to set the value 0.0 %.
To set the limit value, proceed as follows:
1.
>
Parameter >
Compensation > Press
until the de-
sired parameter is displayed.
ð
Z comp. limit value.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The limit value is set.
Cross-monitoring
You can use cross-monitoring to set reciprocal monitoring of 2 devices for
compliance with the set voltage limit values. At least 2 devices with different
CAN bus addresses are needed for cross-monitoring.
6.7.2.1
6.7.2.2
6.8