6 Functions and settings
Maschinenfabrik Reinhausen 2014
55
2374092/04 EN
TAPCON® 260
If you set the switching pulse time to 0 s, the motor-drive unit is activated
with a continuous signal. The signal then remains active for as long as the
or
keys are pressed.
If you set the switching pulse time to 1.5 seconds for example, after the set
delay time T1
or
delay time T2
there will be a switching pulse of 1.5 sec-
onds
.
The waiting time between 2 consecutive switching pulses corresponds to the
set
delay time T1
or
delay time T2
.
Figure 36: Switching pulse time in normal mode
1
Set delay time T1 or T2
2
Set switching pulse time (for
example 1.5 seconds)
If the motor-drive unit does not start with the factory setting (1.5 seconds),
you need to extend the raise switching pulse time / lower switching pulse
time.
If you set the raise switching pulse time or lower switching pulse time to
1.5 seconds, for example
, the next earliest switching pulse occurs in rapid
return control mode
1.5 seconds after the previous switching pulse
ended.
Switching pulse in normal
mode
Switching pulse for rapid
return control