6 Functions and settings
Maschinenfabrik Reinhausen 2014
60
2374092/04 EN
TAPCON® 260
Figure 41: Wiring for motor runtime monitoring
1
Motor running
control input
I/O
3
Motor protective switch
output
relay I/O (optional)
2
Motor protective switch trig-
gered
control input I/O (op-
tional)
4
Motor-drive unit runtime ex-
ceeded
output relay I/O (op-
tional)
If you want to use the output relay, the feedback from the motor-drive unit
Motor protective switch triggered
must also be wired to a control input and
parameterized. This message resets the
Motor runtime exceeded
output re-
lay when the motor protective switch is switched back on and activates the
Motor protective switch triggered
message.
If the runtime monitoring is set to 0.0 seconds this equates to it being
switched off.
To set the motor runtime, proceed as follows:
1.
>
Configuration >
General > Press
until the desired
parameter is displayed.
ð
Motor runtime.
2.
Press
to highlight the position.
ð
The desired position is highlighted and the value can be changed.
3.
Press
to increase the value or
to reduce it.