10 Messages
Maschinenfabrik Reinhausen 2014
145
2374092/04 EN
TAPCON® 260
Relay
Inscription
Cause
IO-X1:20
UNDERVOLT-
AGE
OVERVOLTAGE
OVERCURRENT
Signal for
undervoltage, overvoltage,
overcurrent
message
IO-X1:23
PARALLEL
FAULT, or: See
connection dia-
gram
Signal for
parallel operation error
mes-
sage
IO-X1:25
PARALLEL ON,
or: See connec-
tion diagram
Signal if parallel operation is active
UC-
X1:06...10,
UC-
X1:19...23
TAP POSITION
BCD1…BCD20
BCD signal of tap position
IO-X1:2/3
STATUS
Operating relay
UC1/2/3-
X1:02
ED1/2/3 LOWER
Lower tap position of motor-drive unit
ED1/2/3
UC1/2/3-
X1:04
ED1/2/3 RAISE
Raise tap position of motor-drive unit
ED1/2/3
Table 51: Signal outputs
Event messages
Event message
Cause
Undervoltage
Event message appears if value falls below un-
dervoltage limit value.
Overvoltage
Event message appears if value exceeds over-
voltage limit value.
Overcurrent
Event message appears if value exceeds over-
current limit value.