![MR TAPCON 260 Operating Instructions Manual Download Page 161](http://html.mh-extra.com/html/mr/tapcon-260/tapcon-260_operating-instructions-manual_1844363161.webp)
13 Technical data
Maschinenfabrik Reinhausen 2014
161
2374092/04 EN
TAPCON® 260
Ambient conditions
Operating temper-
ature
-25°C...+70°C
Storage tempera-
ture
-30°C...+85°C
Table 74: Permissible ambient conditions
Tests
Electrical safety
61010-1
Safety requirements for electrical measurement and
control and regulation equipment and laboratory in-
struments
IEC 61131-2
Dielectric test with operating frequency 2.5 kV / 1
min
IEC 60255
Dielectric test with impulse voltage 5 kV, 1.2/50 μs
IEC 60 644-1
Level of contamination 2, overvoltage category III
Table 75: Electrical safety
EMC tests
61000-4-2
Electrostatic discharges (ESD) 6 kV/8 kV
IEC 61000-4-3
Electromagnetic fields (HF) 20 V/m 80...3000 MHz
IEC 61000-4-4
Fast transients (burst) 2 kV
IEC 61000-4-5
Surge transient immunity 4 kV/2 kV/1 kV
IEC 61000-4-6
HF interference immunity (lines) 10 V, 150 kHz...
80 MHz
IEC 61000-4-8
Power frequency magnetic field immunity 30 A/m,
50 Hz, continuous
IEC 61000-4-11
Voltage dips, short interruptions and voltage varia-
tions immunity tests
IEC 61000-4-29
Voltage dips, short interruptions and voltage varia-
tions on DC input power port immunity tests
IEC 61000-6-2
Immunity requirements for industrial environments
IEC 61000-6-4
Emission standard for industrial environments
55011,
DIN EN 55022
Emission "RFI"
Table 76: EMC tests
Environmental durability tests
DIN EN 60529
Degree of protection IP20
IEC 60068-2-1
Dry cold - 25 °C / 96 hours
IEC 60068-2-2
Dry heat + 70 °C/ 96 hours
13.10
13.11
13.11.1
13.11.2
13.11.3
Summary of Contents for TAPCON 260