3 Product description
Maschinenfabrik Reinhausen GmbH 2019
17
6107891/02 EN
ECOTAP
®
VPD
®
3.3 Variants
The ECOTAP® VPD® is available as a 3-phase or 1-phase version.
Type
ECOTAP® VPD® III
ECOTAP® VPD® I
Maximum rated through-current
I
rm
30 A
100 A
30 A
100 A
Highest voltage for equipment
U
m
36 kV
40.5 kV
36 kV
Optional change-over selector
Yes
No
Table 4: ECOTAP® VPD® versions
In the 1-phase version, the connection contacts are arranged on the left or
right side, depending on the order. Figures illustrating this can be found in
the section "ECOTAP® VPD® I without change-over selector" [
For the correct connection, observe the order-specific connection diagram
supplied.
More important information can be found in the "Technical data" [
3.4 Setup/models
The design and designation of the most important on-load tap-changer com-
ponents are shown in the following illustrations. Further details can be found
in the dimensional drawings in the appendix.