11 Technical data
Maschinenfabrik Reinhausen GmbH 2019
73
6107891/02 EN
ECOTAP
®
VPD
®
Rated insulation level (voltage magnitudes for delta applications in kV)
Highest voltage for equipment:
U
m
= 36 kV
U
m =
40.5 kV
U
m =
40.5 kV
Insulation distance
Voltage waveform
Without change-over
selector
Without change-over
selector
With change-over
selector
a
LI 1.2/50 µs
95
95
95
LIC 1.2/50/3…6 µs
105
105
105
AC 50 Hz, 1 min
18
18
18
a1
LI 1.2/50 µs
35
35
35
LIC 1.2/50/3…6 µs
40
40
40
AC 50 Hz, 1 min
6
6
6
b1
1)
LI 1.2/50 µs
200
250
250
LIC 1.2/50/3…6 µs
220
275
275
AC 50 Hz, 1 min
70
95
95
b2
1)
LI 1.2/50 µs
230
305
305
LIC 1.2/50/3…6 µs
250
335
335
AC 50 Hz, 1 min
85
110
110
b3
1)
LI 1.2/50 µs
250
330
330
LIC 1.2/50/3…6 µs
275
360
360
AC 50 Hz, 1 min
100
130
130
f1
LI 1.2/50 µs
200
250
250
LIC 1.2/50/3…6 µs
220
275
275
AC 50 Hz, 1 min
70
95
95
f2
LI 1.2/50 µs
230
305
305
LIC 1.2/50/3…6 µs
250
335
335
AC 50 Hz, 1 min
85
110
110
c1
LI 1.2/50 µs
-
-
120
LIC 1.2/50/3…6 µs
-
-
135
AC 50 Hz, 1 min
-
-
20
c2
LI 1.2/50 µs
-
-
310
LIC 1.2/50/3…6 µs
-
-
340
AC 50 Hz, 1 min
-
-
120
Table 14: Rated insulation level (voltage magnitudes for delta applications in kV)
1)
"b" distances not relevant for ECOTAP® VPD I