6 Commissioning
Maschinenfabrik Reinhausen GmbH 2019
53
6107891/02 EN
ECOTAP
®
VPD
®
4. Press
to confirm the selection.
ð
The LED
lights up and the error code E4.1 is displayed.
6.2 Transporting transformer to the operating site
DANGER
Risk of life-threatening injury due to electric shock!
If the device and system peripherals are not disconnected from the mains,
electric shock may occur!
► De-energize the device and system peripherals and lock them to prevent
them from being switched back on.
NOTICE
Damage to the on-load tap-changer!
Damage to the on-load tap-changer due to incorrect positioning!
► Do not disconnect the motor-drive unit from the on-load tap-changer after
the on-load tap-changer's automatic adjustment.
1. To transport the transformer, disconnect connection cable from control
Section 6.1.1.2, Page 51] section.
2. Wind up connection cable, fix on motor-drive unit, and use plastic film and
adhesive tape to protect from moisture.
3.
NOTICE!
If you do not package the connection cable correctly, moisture
may get in and cause damage to the motor-drive unit.
4. Transport control unit in MR packaging used for delivery.
5.
NOTICE!
The control unit is not intended for operation, transport or stor-
age outdoors.