5 Mounting
Maschinenfabrik Reinhausen GmbH 2019
39
6107891/02 EN
ECOTAP
®
VPD
®
Figure 19: Tap winding connection (example for ECOTAP® VPD® I)
2. If the connection contacts have to be bent, observe the aforementioned
safety notices and use additional pliers to hold in place during bending so
that none of the forces are transferred to the on-load tap-changer. For
reasons of accessibility, we recommend starting with the bottom connec-
tions.
If you have any questions about producing the connections, please contact
Maschinenfabrik Reinhausen GmbH's Technical Service department.
5.3 Mounting motor-drive unit and control unit
As preparation, you must ensure that the on-load tap-changer is in a defined
operating position.
1.
DANGER!
Check the operating position before the transformer is
commissioned or ensure that the transformer is disconnected from all volt-
age sources and secured against reconnection. Failure to do so can lead
to death or serious injuries.