ioLogik E1200 Series
Modbus/TCP Default Address Mappings
A-14
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference
Address
Data Type
Description
40033
0x0020
1 word
DO all Value (Ch0~3)
Bit0 = Ch0 DO Value (0=OFF, 1=ON)
Bit3 = Ch3 DO Value (0=OFF, 1=ON) …… …
Bit4 to 15 = reserved
E1260 Modbus Mapping
3xxxx Read Only Registers (Function 4)
Reference
Address
Data Type
Description
31537
0x0600
1 word
CH0 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31538
0x0601
1 word
CH1 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31539
0x0602
1 word
CH2 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31540
0x0603
1 word
CH3 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31541
0x0604
1 word
CH4 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31542
0x0605
1 word
CH5 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
E1262 Modbus Mapping
3xxxx Read Only Registers (Function 4)
Reference
Address
Data Type
Description
32049
0x0800
1 word
CH0 TC Minimum Value Hi Word
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
32050
0x0801
1 word
CH0 TC Minimum Value Lo Word
Hi+Lo Range: 0~4294967295
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
32051
0x0802
1 word
CH1 TC Minimum Value Hi Word
32052
0x0803
1 word
CH1 TC Minimum Value Lo Word
32053
0x0804
1 word
CH2 TC Minimum Value Hi Word
32054
0x0805
1 word
CH2 TC Minimum Value Lo Word
32055
0x0806
1 word
CH3 TC Minimum Value Hi Word
32056
0x0807
1 word
CH3 TC Minimum Value Lo Word
32057
0x0808
1 word
CH4 TC Minimum Value Hi Word
32058
0x0809
1 word
CH4 TC Minimum Value Lo Word
32059
0x080A
1 word
CH5 TC Minimum Value Hi Word
32060
0x080B
1 word
CH5 TC Minimum Value Lo Word
32061
0x080C
1 word
CH6 TC Minimum Value Hi Word
32062
0x080D
1 word
CH6 TC Minimum Value Lo Word
32063
0x080E
1 word
CH7 TC Minimum Value Hi Word
32064
0x080F
1 word
CH7 TC Minimum Value Lo Word