ioLogik E1200 Series
Using the Web Console
3-3
Network Settings
General Settings
On the General Settings page, you can assign a server name and location to assist you in differentiating
between different ioLogik E1200 units. You may also configure the Modbus/TCP idle interval or enable the
Communication Watchdog function.
The Connection Watchdog activates the safe status (Safe Mode) when the ioLogik E1200 loses its network
connection for the specified amount of time. Safe Mode is designed especially for products that have output
channels to output a suitable value or status when the ioLogik E1200 cannot be controlled by a remote PC (due
to network failure, for example). By default, the Watchdog is disabled. Users can configure how each output
channel responds on the I/O Settings page.
To enable the Watchdog, check
Enable connection watchdog
, set the timeout value, and then restart the
server. With Watchdog enabled, the ioLogik E1200 will enter Safe Mode after there is a disruption in
communication that exceeds the time specified.