Ix350_02b_oi_e.doc / Mai-18
Page 33 / 50
5.9.
Analog Menu
This menu defines the basic settings of the analog output.
This function is only available for devices with option AO.
ANALOG FORMAT
This parameter defines the output characteristics. The analogue output is proportional to the display value.
With setting ANALOG FORMAT (-10 … +10 V) in MODE COUNTER the polarity of the analog output depends on
the polarity of the display value.
0
-10…10V
-10 … +10 V
1
0…20MA
0 … 20 mA
2
4…20MA
4 … 20 mA
ANALOG START
This parameter defines the start value of the analog conversion. This start value is corresponding to the display
value for an analog output of 0 V or 0/4 mA.
-99999999
Smallest start value
0
Default value
+99999999
Highest start value
ANALOG END
This parameter defines the end value of the analog conversion. This end value is corresponding to the display
value for an analog output of (+/-) 10 V or 20mA.
-99999999
Smallest end value
10000
Default Wert
+99999999
Highest end value
ANALOG GAIN (%)
This parameter defines the zero offset of the analog output. The ANALOG GAIN is the maximum modulation of
the analog output in % terms given up to (+/-) 10 V or 20 mA.
E.g. 102,00 results in an offset of 10.2 V / 20.4 mA from reaching the ANALOG START value
E.g. 95,00 results in an offset of 9.5 V / 18 mA from reaching the ANALOG END value
0,00
Smallest end value
100,00
Default Wert
110,00
Highest end value
ANALOG OFFSET (%)
This parameter defines the zero offset of the analog output.
E. g. 0.20 results in an offset of 0.02 V or 0.04 mA from reaching the ANALOG START value
-99,99
Smallest offset
0
Default value
+99,00
Highest offset