5.2
IN 1 Properties
This menu defines the parameter for input 1.
CONFIGURATION
This parameter defines the configuration of input 1.
0 -10 … 10 V
-10 … 10 V
1 0 … 20 MA
0 … 20 mA
2 4 … 20 MA
4 … 20 mA
START VALUE
This parameter defines the dispay value of an input signal of 0V, 0mA or 4mA. Signal values between START VALUE
and END VALUE behave proportional.
-99999
Smallest start value
0
Default value
99999
Highest start value
END VALUE
This parameter defines the dispay value of an input 10V bzw. 20mA.
Signal values between START VALUE and END VALUE behave proportinal.
-99999
Smallest end value
10000
Default value
99999
Highest end value
DECIMAL POINT
This value defines the position of the decimal point.
0 NO
No decimal point
1 0000000.0
Decimal point at the specified position
2 000000.00
Decimal point at the specified position
3 00000.000
Default decimal point at the specified position
4 0000.0000
Decimal point at the specified position
5 000.00000
Decimal point at the specified position
6 00.000000
Decimal point at the specified position
7 0.0000000
Decimal point at the specified position
SCALE UNITS
This parameter defines the required engineering unit. This parameter does not affect the calculation of the display
value. The number of decimal places must be defined with the parameter DECIMAL POINT. A list of available units
can be found in Chapter 6.2 Appendix: Display of scale units.