By340_04b_oi_e.doc / Apr-16
Page 30 / 42
Unconnected NPN inputs are always HIGH (internal pull-up resistor)
Unconnected PNP inputs are always LOW (internal pull-down resistor)
When you use Index operation, it is mandatory to use
Control Input 1 as Master Index (F06.050 = 12) and
Control Input 2 as Slave Index (F06.052 = 11).
These two inputs are no more available for other purpose.
Index inputs must always be edge-triggered, i.e. parameters F06.049 and F06.051
must be either 2 or 3 or 6 or 7 when you use index operation.
Where you like visualize Index Signals on your PC screen by means of the OS32
Operator Software, you must temporary set the inputs to static operation. The
corresponding light boxes on the screen are not suitable to display dynamic
signals. Please return to edge- triggered operation after the test.
8.2.8.
Serial communication parameters
F07
Range
Default
F07.058 Serial device address (unit number)
11 … 99
11
F07.059 Serial baud rate
0 … 6
0
0= 9600 Baud
1= 4800 Baud
2= 2400 Baud
3= 1200 Baud
4= 600 Baud
5= 19200 Baud
6= 38400 Baud
F07.060 Serial data format
0 … 9
0
0= 7 Data, Parity even, 1 Stop
1= 7 Data, Parity even, 2 Stop
2= 7 Data, Parity odd, 1 Stop
3= 7 Data, Parity odd, 2 Stop
4= 7 Data, no Parity, 1 Stop
5= 7 Data, no Parity, 2 Stop
6= 8 Data, Parity even, 1 Stop
7= 8 Data, Parity odd, 1 Stop
8= 8 Data, no Parity, 1 Stop
9= 8 Data, no Parity, 2 Stop