By340_04b_oi_e.doc / Apr-16
Page 33 / 42
9.2.
Outputs
No.
Output
Terminal
K1
Alert 1
This output indicates that the position error has exceeded the
preset tolerance band as specified by parameter F02.16 “Alert 1”
X2 / 26
K2
Alert 2 / Index ok
When operating without index pulses, this output also works as
alert signal. It then indicates that the position error has exceeded
the preset tolerance band as specified by parameter F02.17
“Alert 2”.
With index operation (Parameter F02.004 „Operation Mode“ = 2,
6 or 8), K2 works as “Index ok” output. It then indicates that the
slave index is within the preset tolerance band as defined by
parameter F02.022 “Index Window”.
X2 / 25
K3
Max. Correction
Indicates that the limitation of the correction voltage has been
activated to keep the correction inside “Max. Correction”
X1 / 10
K4
Max. Frequency
Indicates that the actual master frequency is higher than the limit
set by parameter F02.013 “Max. Master Frequency”
X1 / 9