By340_04b_oi_e.doc / Apr-16
Page 29 / 42
8.2.7.
Characteristics and functions of the Control Inputs
F06
Range
Default
F06.049 Switching characteristics of input „Cont.1“
0 … 7
0
0=
NPN (switch to -), function active LOW
1=
NPN (switch to -), function active HIGH
2=
NPN (switch to -), rising edge
3=
NPN (switch to -), falling edge
4=
PNP (switch to +), function active LOW
5=
PNP (switch to +), function active HIGH
6=
PNP (switch to +), rising edge
7=
PNP (switch to +), falling edge
F06.050 Function assignment to input „Cont.1“
0 … 16
6
0=
No function
1=
Reset
2=
Trim -
3=
Trim +
4=
n. a.
For more details about these
functions see section
9.1
5=
n. a.
6=
Integrator off
7=
Store EEProm
8=
Scroll Display
9=
Parameter Disable
10= Clear Min. & Max.
11= Index Slave
12= Index Master
13= n. a.
14= Read front thumbwheels (model 641 only)
15= Stop Slave
16= n. a.
F06.051 Switching characteristics of input „Cont.2“
See „Cont.1“ (F06.049)
F06.052 Function assignment to input „Cont.2“
See „Cont.1“ (F06.050)
F06.053 Switching characteristics of input „Cont.3“
See „Cont.1“ (F06.049)
F06.054 Function assignment to input „Cont.3“
See „Cont.1“ (F06.050)
F06.055 Switching characteristics of input „Cont.4“
0 – 3
0= NPN (switch to -) function active LOW
no edge-triggered functions are
possible with Cont.4
1= NPN (switch to -) function active HIGH
2= PNP (switch to +), function active LOW
3= PNP (switch to +), function active HIGH
F06.056 Function assignment to input „Cont.4“
See „Cont.1“ (F06.050)
n. a. = not applicable