Series Digital Solid State Soft Starter User Manual
90 |
P a g e
5.5.15 Motor Power Protection Settings
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F102
P
owe
r
P
rot
e
c
ti
o
n
Motor KW Trip
0 - 2
0 = Disabled
1 = Over KW Trip
2 = Under KW Trip
1
0
F103
Motor KW Trip Point
20 - 100% of full load KW
1%
50(%)
F104
Motor KW Trip Delay Time
1 - 999 seconds
1
1
F105
Power Factor Trip Range
0, 1 - 3 [0=Disabled, 1=lag, 2=lead,
3= lead/lag]
1
0
F106
Power Factor Trip Point
.01 - 1
.01
.50
F107
Power Factor Trip Delay Time 1 - 20 seconds
1
2
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F108
P
owe
r
P
rot
e
c
ti
o
n
Analog Output
0 - 12, 0: OFF;
See Page 62 for settings.
1
OFF
F109
Analog Output 4mA
0 - 9999
1
0
F110
Analog Output 20mA
0 - 9999
1
9999
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F111
S
y
s
te
m
S
e
tt
ings
Default Display
1 - 12 (See Table of Default Display)
1
10
F112
System Settings
Reserved for factory
-
-
F113
Alternate functions for
Ramp2/Jog inputs
See Table page 64
1