Series Digital Solid State Soft Starter User Manual
33 |
P a g e
5.5.9
Lockouts, Reset and Internal Protection Functions
5.5.10 Output Relay Programming Features
Notes:
Check wiring to each relay before changing programming to ensure
there are no unintended consequences.
Relays programmed to some protection features will not operate if
function is disabled elsewhere.
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F048
Lock
outs
,
R
e
s
e
t
a
nd
Int
e
rna
l
P
rot
e
c
ti
on
Coast Down (Back Spin)
Lockout Timer
0 - 60 minutes
[0 = Disabled]
1 minute
0
Disabled
1
5.6.9
F049
Maximum Starts per Hour
0 - 10 starts
[0 = Disabled]
1
0
Disabled
F050
Minimum Time Between
Starts
0 - 60 minutes
[0 = Disabled]
1 minute
0
Disabled
F051
nCP Trip (No Control Power)
0, 1 [0=Disabled, 1=Enabled]
1
0
1
5.6.9.a
F052
Auto Reset
on Selected Faults
Fault Preferences 1 - 17
See Table 5.6.7:
”Auto-Reset Selected Faults”
1
4,
Phase
Loss only
1
5.6.9.b
F053
Auto Reset Attempts
0 - 10 attempts
[0 = Disabled]
[In 1 minute cycle]
1
0
Disabled
F054
Restart Delay Time Value
Readout (for F028)
0 - 999 Seconds
-
Read
Only
Read
Only
5.6.9.c
F055
Coast Down Timer Value
for F048
1 - 3600 Seconds
-
Read
Only
F056
Starts Per Hour Timer Value
for F049
1 - 3600 Seconds
-
Read
Only
F057
Starts Per Hour
For F049
1 - 10 Starts
-
Read
Only
F058
Time Value Between Starts
for F050
1 - 3600 Seconds
-
Read
Only
F059
Thermal Capacity to Start
for F005
0 - 100 % Thermal Capacity
-
Read
Only
Table 5.5.9: Lockouts, Reset and Internal Protection Group
Fn # Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F060
Out
put Re
la
y
s
Aux Relay 1 setting
Operation # 1 - 32: see
”Aux. Relay Settings Chart”
1
1
1
5.6.10
F061
Aux Relay 2 setting
Operation # 1 - 32: see
”Aux. Relay Settings Chart”
1
2
F062
Aux Relay 3 setting
Operation # 1 - 32: see
”Aux. Relay Settings Chart”
1
22
F063
Aux. Relay Delay Timer
(for Operations 28-31)
0 - 999 seconds
[0 = Disabled]
1 second
0
No Delay
F064
Reserved for factory use
2
Table 5.5.10: Output Relay Function Group