Series Digital Solid State Soft Starter User Manual
36 |
P a g e
5.5.15 Motor Power Protection Settings
5.5.16 Analog Output
5.5.17 Display and System Settings
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F102
P
owe
r
P
rot
e
c
ti
o
n
Motor kW Trip
0 - 2
0 = Disabled
1 = Over kW Trip
2 = Under kW Trip
1
0
1
5.6.15
F103
Motor kW Trip Point
20 - 100% of full load KW
1%
50(%)
F104
Motor kW Trip Delay Time
1 - 999 seconds
1
1
F105
Power Factor Trip Range
0, 1 - 3 [0=Disabled, 1=lag,
2=lead, 3= lead/lag]
1
0
F106
Power Factor Trip Point
.01 - 1
.01
.50
F107
Power Factor Trip Delay Time
1 - 20 seconds
1
2
Table 5.5.15: Motor Power Protection Function Group
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F108
P
owe
r
P
rot
e
c
ti
o
n
Analog Output
0 - 12
[0: OFF; 1 - 12]
(See Table of Default Display)
1
OFF
1
5.6.16
F109
Analog Output 4mA
0 - 9999
1
0
F110
Analog Output 20mA
0 - 9999
1
9999
Table 5.5.16: Analog Output
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Password
Level
Section
F111
S
y
s
te
m
S
e
tt
ings
Default Display
1-12 (See Table of Default
Display)
1
10
1
5.6.17
F112
System Settings
Reserved for factory use
-
-
2
F113
Alternate functions for
Ramp2/Jog inputs
See Table page 64
1
7
1
Table 5.5.17: System Settings