Series Digital Solid State Soft Starter User Manual
54 |
P a g e
5.6.10 Output Relays
There are three programmable relays (rated 240VAC, 5A, 1200 VA) in
the
VMX2 Series
. They can be programmed for change of state
indication for any one of the 32 conditions identified in the following
chart.
F060 = Aux Relay 1: Form C (SPDT)
Factory Setting = 1 (Run / Stop)
Range = 1 - 32 (See list)
Use to program the desired operation for Relay # 1.
F061 = Aux Relay 2: Form C (SPDT)
Factory Setting = 2 (At Speed / Stop)
Range = 1 - 32 (See list)
Use to program the desired operation for Relay # 2.
F062 = Aux Relay 3: Form A (SPST, N.O.)
Factory Setting = 22 (Any Trip, 5 - 15)
Range = 1 - 32 (See list)
Use to program the desired operation for Relay # 3.
F063 = Aux Relay Delay Timer for Settings 28 - 31
Factory Setting = 0 (Disabled)
Range = 1 - 999 seconds, or 0 (Disabled)
Use to program the desired On Delay for any Aux. Relay that
has been programmed for Settings 28 through 31 from the chart
below.
F064 = Reserved
Setting
Relay Operation Description
Setting
Relay Operation Description
1
Run / Stop
17
Over Voltage Trip
2
At Speed / Stop
18
Under Voltage Trip During Start
3
At Speed / End of Decel
19
Under Voltage Trip During Run
4
Start / End of Decel
20
Power Factor Trip
5
Short SCR Trip
21
Power Trip
6
Phase Loss Trip
22
Any Trip
7
Shunt Trip
23
Any Trip, flashing output
8
OL Trip
24
Coast Down Time Lockout
9
OT Trip
25
Starts Per Hour Lockout
10
Short Circuit Trip
26
Time Between Starts Lockout
11
Current Imbalance Trip
27
Any Lockout
12
Over Current Trip
28
Run / Stop with On-delay from F063
13
Under Current Trip
29
At Speed / Stop with On-delay from F063
14
Ground Fault Trip
30
At Speed / End of Decel with On-delay from F063
15
Phase Rotation Trip
31
Start / End of Decel with On-delay from F063
16
Voltage Imbalance Trip
32
Power Loss (nCP No Control Power) Trip
*Note: Flash rate for Setting #23 is ½ second On and Off
Table 5.6.9: Output Relay Programming