Series Digital Solid State Soft Starter User Manual
84 |
P a g e
Appendix 5 - Soft Starter Settings Record
The following chart may be used to record the changes made to the factory settings.
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F001
Mo
tor
a
nd
Ov
e
rl
oad
I
nf
o.
Motor Nameplate FLA
FLA must be programmed for
starter to function.
50 - 100% of Max Amp Rating.
Upper limit of range
automatically adjusts downward
as Service factor is increased.
1 amp
0
F002
Motor Nameplate
Service Factor
1.00 - 1.30 SF
0.05
1.0 SF
F003
Overload Class During Start
NEMA / UL Class 5 - 20
5
Class 10
F004
Overload Class During Run
NEMA / UL Class 5 - 30
5
Class 10
F005
Overload Reset
0 = Manual
1 = Auto
2 = Disabled Overload
1
0
(Manual)
F006
-
F009
Reserved for factory use
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F010
S
ta
rt
ing
a
nd
S
top
pi
n
g
Mo
des
Ramp Type Selection:
VR = Voltage Ramp
CR = Current PID Ramp
1 = Ramp 1, 2 = Ramp 2
Setting 1 = VR1 + VR2
Setting 2 = CR1 + CR2
Setting 3 = VR1 + CR2
Setting 4 = CR1 + VR2
1
1
VR1+VR2
F011
Initial Torque (VR) of Ramp 1
0 - 100% Line Voltage
1%
60%
F012
Initial Torque (CR) of Ramp 1
0 - 600% Motor
Current
1%
200%
F013
Accel Ramp Time of Ramp 1
1 - 120 seconds
1 second
10
seconds
F014
Max Current Limit of Ramp 1
200 - 600% Motor
Current
1%
350%
F015
Initial Torque (VR) of Ramp 2
0 - 100% Line Voltage
1%
60%
F016
Initial Torque (CR) of Ramp 2
0 - 600% Motor
Current
1%
200%
F017
Accel Ramp Time of Ramp 2
1 - 120 seconds
1 second
10
seconds
F018
Max Current Limit of Ramp 2
200 - 600% Motor
Current
1%
350%