![motortronics VMX2 SERIES User Manual Download Page 88](http://html1.mh-extra.com/html/motortronics/vmx2-series/vmx2-series_user-manual_1839364088.webp)
VMX
2
Series Digital Solid State Soft Starter User Manual
86 |
P a g e
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F29
Li
ne
V
o
lt
a
ge
Voltage Input
200 - 690 Volt
1
480
F030
Voltage Imbalance Trip %
0, 1 - 30% [0=Disabled]
1(%)
0
F031
Voltage Imbalance Trip Delay
1 - 20 seconds
1
10
F032
Over Voltage Trip %
0, 1 - 10% [0=Disabled]
1(%)
0
F033
Over Voltage Trip Delay
1 - 20 seconds
1
10
F034
Under Voltage Trip on Start %
0, 1 - 20% [0=Disabled]
1(%)
0
F035
UV Trip on Start Delay
1 - 180 seconds
1
10
F036
Under Voltage Trip on Run %
0, 1 - 20% [0=Disabled]
1(%)
0
F037
UV Trip Delay during Run
1 - 20 seconds
1
2
F038
Shorted SCR and Trip Delay
0, 1-10 seconds [0=Disabled]
1 second
1 second
F039
Shunt Trip Delay
0, 1-10 seconds [0=Disabled]
1 second
1 second
Fn #
Group
Function Description
Adjustment / Display Range
Setting
Increments
Factory
Setting
Setting
F040
P
has
e
C
urre
nt
Current Imbalance Trip
0 = Disabled, or
5 - 30% imbalance
1%
0
Disabled
F041
Current Imbalance Trip Delay
1 - 20 seconds
1 second
2
seconds
F042
Over Current Trip
0 = Disabled, or
100 - 300% of motor FLA
1%
0
Disabled
F043
Over Current Trip Delay
1 - 20 seconds
1 second
1 second
F044
Under Current Trip
0 = Disabled, or
10 - 90% of motor FLA
1%
0
Disabled
F045
Under Current Trip Delay
1 - 60 seconds
1 second
2
seconds
F046
Ground Fault Trip
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1%
0
Disabled
F047
Ground Fault Trip Delay
1 - 60 seconds
1 second
2
seconds