2.6.1
Power Terminals:
Connection points are bus tabs with pre-drilled holes (see below).
Suggested wire sizes and tightening torques for factory-supplied
connectors using conductors rated for 75
C are shown in the chart
below. Always consult local and national codes along with industry
standard practices for proper wires sizes and terminations to
accommodate voltage drop and ambient conditions.
Table 2.6: VMX2 Series Wire Ranges and Torque Specifications
Model
Number
Current Range
Min.- Max.
Suggested
Wire Size
AWG
Tightening
Torque
in.-lbs.
Screw / Bolt
Size
Tightening
Torque
Nm
Suggested
Wire Size
ISOmm
2
VMX2-18-BP
9 - 18
10
35
1 x M5
(included)
4
6
VMX2-28-BP
14 - 28
8
10
VMX2-39-BP
19 - 39
8
10
VMX2-48-BP
24 - 48
6
16
VMX2-62-BP
36 - 62
4
45
1 x M8
(included)
5
25
VMX2-78-BP
39 - 78
3
35
VMX2-92-BP
46 - 92
2
35
VMX2-112-BP
56 - 112
1
50
VMX2-150-BP
75 - 150
2/0
80
1 x M8
(included)
9
70
VMX2-160-BP
80 - 160
3/0
95
VMX2-210-BP
105 - 210
250
200
1 x 0.38" hole
(M10)
for User
supplied
lugs
15
150
VMX2-275-BP
138 - 275
350 kCMIL
185
VMX2-361-BP
180 - 361
2 x 300 kCMIL
2 x 150
VMX2-450-BP
225 - 450
2 x 300 kCMIL
2 x 150
VMX2-550-BP
275 - 550
2 x 400 kCMIL
2 x 240
VMX2-600-BP
300 - 600
2 x 500 kCMIL
TBD
TBD
TBD
2 x 300
VMX2-862-BP
431 - 862
3 x 400 kCMIL
TBD
TBD
TBD
3 x 240
VMX2-900-BP
450 - 900
3 x 500 kCMIL
TBD
TBD
TBD
3 x 300
VMX2-1006-BP
503 - 1006
4 x 350 kCMIL
TBD
TBD
TBD
4 x 185
VMX2-1250-BP
625 - 1250
4 x 500 kCMIL
TBD
TBD
TBD
4 x 300
Note: TBD = To Be Determined at a later date
2.7
Remote Keypad Mounting
The keypad / operator interface unit can be remotely mounted up to 10ft
(3 meters) away from the starter, i.e. on the enclosure door. A remote
mounting kit is necessary, which consists of an adaptor plate, a
doorframe for NEMA 1 or NEMA 12 enclosures and a pre-assembled
ribbon cable available in 1-meter length increments. Detailed assembly
instructions and an enclosure cutout template are included with the kit.
See Product Selection Guide for part numbers of the available kits.
Figure 2.7
Remote Keypad Mounting Kit
Components
VMX2 Starter
Adaptor Plate
NEMA12
Door Frame
Ribbon Cable,
1, 2, or 3 Meters
(3.28, 6.56, or 9.84 feet.)