9 Devices
Rev. 06/2021
113
–
MAP Turbo
For normal operation detection of the NO
X
monitor, the absolute charging pressure of a
turbo engine serves as an indicator for the engine load. For this purpose, a manifold
pressure sensor must be connected to input 3 of the respective CAN bus module (see
Wiring of Manifold Pressure Sensor, MAP Signal, Load Signal
on page 64).
–
Load on CAN Module
The NO
X
monitor detects normal operation by means of the load signal connected to in-
put 3 of the respective CAN bus module (see
Wiring of Manifold Pressure Sensor, MAP
Signal, Load Signal
on page 64).
–
Load via CANopen
The NO
X
monitor detects normal operation by means of the load signal connected to the
analog input of the optional I/O communication module. For this purpose, the function
Load Input for NOx
must be assigned to the analog input of the respective I/O communi-
cation module (see
Analog Inputs
on page 125).
–
Start/Stop via CANopen
The NO
X
monitor receives the normal operation release from the master control via a bi-
nary signal connected to the binary input of the optional I/O communication module. For
this purpose, the function
Normal Operation Release for NOx
must be assigned to the bi-
nary input of the respective I/O communication module (see
Binary Inputs
on page 123).
–
Scaling Min., Scaling Max.
Via these entries you can specify the measuring value range of the absolute manifold pres-
sure sensor in the NO
X
monitoring modes
MAP Naturally Aspirated
and
MAP Turbo
. Under
Scaling Min.
, enter the measured value of the sensor at 4 mA and under
Scaling Max.
at
20 mA. The values in-between are interpolated linearly.
–
MAP < / MAP > / Last / ---
The entry displayed at this point depends on the set NO
X
monitoring mode:
–
MAP <
In the NO
X
monitoring mode
MAP Naturally Aspirated
you set the absolute charging
pressure which must be undercut for normal operation detection (see
Determining Char-
ging Pressure for Normal Operation Detection
on page 57).
–
MAP >
In the NO
X
monitoring mode
MAP Turbo
, you set the absolute charging pressure which
has to be exceeded for normal operation detection (see
Determining Charging Pressure
for Normal Operation Detection
on page 57).
–
Load
In the NO
X
monitoring modes
Load on CAN Module
and
Load via CANopen
, you specify
the load that indicates the beginning of normal operation of your engine (for example 30
% nominal load as per VDMA 6299:2019-09 or as per the engine manufacturer's specifi-
cations).
Summary of Contents for EasyNOx
Page 1: ...EasyNOX NOX Monitoring Operating Manual P N 01 50 026 EN Rev 06 2021 ...
Page 33: ...4 Product Description Rev 06 2021 33 4 1 7 Overview Drawings 4 1 7 1 Dimensions EasyNOX ...
Page 34: ...4 Product Description 34 Rev 06 2021 ...
Page 35: ...4 Product Description Rev 06 2021 35 CAN Bus NOX Sensor Module P N 63 05 015 ...
Page 36: ...4 Product Description 36 Rev 06 2021 I O Communication Module Optional ...
Page 142: ......