9 Devices
Rev. 06/2021
123
9.2.2.1
Binary Inputs
The
Binary Inputs
button in the
Preferences
view of an added I/O communication module opens
the
Binary Inputs
view.
Note that changes in this view are not saved and applied by the I/O communication module until
you exit the view. Use the drop-down list to link the binary input of the I/O communication mod-
ule displayed in the
Ch.
(Channel) column to the following functions:
–
Not Used
The binary input is not linked to any function.
–
Normal Operation Release for NOx1 / NOx2
A master control can signal to the respective NO
X
monitor of the EasyNO
ₓ
via a closed binary
input that the conditions for normal operation are met by the engine. In NO
X
monitoring
mode
Start/Stop via CANopen
, the binary input must be linked to this function.