background image

 

The Interface Solution Experts 

31

SPA

Site-Programmable  Volt & 

Milliamp Limit Alarm Trips

22. Press SELECT to access the high/low 

setting screen, or use the arrow buttons 
to scroll through the other alarm operating 
parameters.  Press SELECT to access the 
screen(s) for the parameter displayed, or 
scroll to “EXIT ALRM” and press SELECT 
to access the menus for another alarm (if 
installed), or to return to the Main Menu.

SET HI/LO

23. From the “SET HILO” screen, press 

SELECT.

24. Use the arrow buttons to toggle the alarm 

function between high alarm operation 
(trips when input exceeds the trip point 
setting) and low alarm operation (trips 
when input drops below the trip point).

25. Press SELECT when the display shows 

the desired setting.  This returns the unit 
to the Alarm Configuration menu at “SET 
LAT” (choose latching or non-latching 
alarm function).

26. Press SELECT to access the latch/no 

latch setting screen, or use the arrow 
buttons to scroll through the other alarm 
operating parameters.  Press SELECT to 
access the screen(s) for the parameters 
displayed, or scroll to “EXIT ALRM” and 
press SELECT to access the menus for 
another alarm (if installed), or to return to 
the Main Menu.

SET LATCHING/NON-LATCHING

27. From the “SET LAT” screen, press 

SELECT.

28. Use the arrow buttons to toggle the 

alarm function between latching (alarm 
stays tripped until input returns to normal 
(allowing for any deadband) AND unit is 
manually reset) and non-latching (alarm 
returns to normal as soon as input returns 
to normal, allowing for any deadband) 
function.

29. Press SELECT when the display shows 

the desired setting.  This returns the unit 
to the Alarm Configuration menu at “EXIT 
ALRM”.

30. Press SELECT to bring up the menu for 

the next installed alarm.  If no additional 
alarms are installed, or to return to the 
Main Menu, press SELECT from “EXIT 
ALRM”.

 

To set the operating parameters for the 
next installed alarm, use the arrow buttons 
from the “EXIT ALRM” screen to display 
the next alarm, “AL2 CONF”, for example, 
and press SELECT, and return to step 3.

 

When all of the alarm parameters for all 
of the installed alarms have been set 
as desired, press SELECT from “EXIT 
ALRM”, and press SELECT again from 
“ALRM EXIT”.  This returns the unit to the 

Main Menu at “PASS WORD”

 

Summary of Contents for SPA HLPRG

Page 1: ...The Interface Solution Experts 1 SPA SPAApril 2016 224 715 00D Site Programmable Volt Milliamp Limit Alarm Trips HLPRG Site Programmable Volt Mil liamp Limit Alarm Trips...

Page 2: ...ush Buttons Inactive during operation Inactive during operation SELECT Use or push buttons to scroll through menus and sub menus Use SELECT push button to access menu and or make a choice VIEW SEL V I...

Page 3: ...Password 11 Select Input Type 12 Configure Function Options 13 Scaling Input Smart Scaling the HLPRG 15 Applying Input Bench Ranging the HLPRG 17 Scaling the Display Setting the Engineering Units in C...

Page 4: ...Mode the SPA HLPRG behaves much like a simple input meter The display is set by the user to show the input in either mA or volts Its scaling is tied to any input scaling performed If equipped with th...

Page 5: ...lity and adjustment resolution Response Time 250 msec maximum time for output to go from 10 to 90 for step change on input Ripple up to 120Hz Current output 10mV peak to peak max when measured across...

Page 6: ...all for a buffer zone or Deadband around the trip point to allow for minute fluctuations in the process input In the SPA the reset point is determined by the deadband setting Latching SPA alarms will...

Page 7: ...e location of each of the controls for setting Password Security ON OFF Figure 2 Failsafe Non failsafe Alarm Function Figure 3 Current Source Sink or Voltage Figure 4 Available in AO equipped SPAs onl...

Page 8: ...n Failsafe Alarm Function FAILSAFE NON FAILSAFE SET FAILSAFE NON FAILSAFE 1 2 3 4 EXAMPLE ALARMS 1 2 NON FAILSAFE ALARMS 3 4 FAILSAFE BACK NO1 CM1 NC1 NO2 CM2 NC2 GND RELAY 1 RELAY 2 POWER AC OR DC FR...

Page 9: ...e Custom Mode only Scale Analog Output AO equipped units only Trim Analog Output AO equipped units only Configure Alarm Functions Trip points etc Change View Password Main Menu View Settings Figure 5...

Page 10: ...D OR TO UNLESS IN CUSTOM MODE VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT IN...

Page 11: ...not known the unit settings can be viewed but not changed as shown in Figure 17 4 If you have entered the correct password the Select Input Type menu SEL V I will be accessed If not the display will s...

Page 12: ...o options for input type The default display for this menu is always the last setting 3 When the display shows the type of input current or voltage that is to be used with the SPA press SELECT 4 The n...

Page 13: ...rom the CONF OPTS screen of the Main Menu press SELECT This brings up SET FUNC which is the access screen for choosing between Linear and Custom Function Modes 2 Press SELECT again to set the desired...

Page 14: ...PTS CONF OPTS LIN OFF LIN ON LIN ON LIN OFF DEGC SEL V I CONF OPTS SET FUNC CUST FUNC LINR FUNC SET EGU DEGC DEGF PCT BLNK CSTM EXIT OPTS LIN OFF LIN ON EXIT OPTS SET LIN CUST FUNC LINR FUNC WHAT IS T...

Page 15: ...o EXIT SCLE to abort Smart Scaling and return to the Main Menu 3 When the desired parameter shows on the LCD press SELECT The LCD will show the engineering units selected in Configure Options menu dis...

Page 16: ...SEL V I APLY INPT EXIT SCLE SET ZERO CUST FUNC CONF OPT SCLE DSPL SCLE AO WAS SELECTED IN YES NO CONF OPT SCLE INPT SET ZERO SET FULL EXIT SCLE XXXX MA XXXX VOLT XXXX MA XXXX VOLT INCREMENT XXXX ZERO...

Page 17: ...e Options menu discussed earlier in this section 4 Vary the input to either the zero or full scale level from the intended application 5 When the display shows the appropriate readout press SELECT to...

Page 18: ...ODE OF THE UNIT WAS SELECTED IN WAS SELECTED IN AND UNIT IS EQUIPPED WITH AO WAS SELECTED IN EXIT APPLY INPUT AND RETURN TO THE MAIN MENU SMART SCALING VIEW SELECT VIEW SELECT VIEW SELECT VIEW SELECT...

Page 19: ...values changed appropriately in order to carry any scaling changes through to the display Figure 12 shows the menu for this procedure 1 From the SCLE DSPL screen of the Main Menu press SELECT 2 Use t...

Page 20: ...ION INSTALLED NO YES XXXX EGU XXXX EGU XXXX VOLT SET DP DSPL ZERO DSPL FULL EXIT DSPL APLY INPT SCLE DSPL SMART SCALING SHIFTS DECIMAL TO THE RIGHT SHIFTS DECIMAL TO THE LEFT SETS DECIMAL POSITION INC...

Page 21: ...zero and full scale values have been entered into memory for Input scaling smart scaling or input capturing bench scaling Display scaling Analog Output if present 2 From the ENTR CURV point of the ma...

Page 22: ...oint to be programmed if the NUMB PNTS value was changed or returns to the ENTR PNT screen to allow the user to select the next point From ENTR PNT the user can also exit to the main menu NOTE When pr...

Page 23: ...ut zero in this case 0mA and Xf Input full scale in this case 50mA Xn Xn 1 through Xn 19 Input curve Yz Yn Yn 1 Yn 2 Yn 19 Yf Where Yz Display zero in this case 0 and Yf Display full scale in this cas...

Page 24: ...be added the SPA menu automaticalles takes the user to the point that has not yet been defined The user cannot exit the curve programming until all points are defined NOTES If INPUT SCALING X axis is...

Page 25: ...note of the scaling for future reference and press SELECT 6 Repeat steps 2 through 5 until all parameters for the display have been set as required 7 With EXIT Z FS showing on the LCD press SELECT to...

Page 26: ...AO SET ZERO SET FULL EXIT Z FS XXXX MA XXXX VOLT XXXX MA XXXX VOLT SMART SCALING DEFAULTS TO LAST SELECTED INCREMENTS OUTPUT ZERO DECREMENTS OUTPUT ZERO INCREMENTS OUTPUT FULL SCALE DECREMENTS OUTPUT...

Page 27: ...VOLTAGE SOURCE _ CURRENT SOURCE _ MULTIMETER OR MILLIAMETER _ _ AC OR DC POWER SUPPLY GND VIEW SELECT SPA SITE PROGRAMMABLE ALARM READY INPUT TRIP 1 TRIP 2 TRIM OUT TRIM ZERO TRIM ZERO TRIM FULL TRIM...

Page 28: ...xit NOTES There are two options for setting the trip points of the installed alarms ENTR TRIP and APLY TRIP In the ENTR TRIP menu the user employs the Smart Ranging feature of the SPA entering the des...

Page 29: ...FROM THE MAIN MENU HIGHEST NUMBERED INSTALLED ALARM IS ANOTHER ALARM INSTALLED NEXT HIGHEST NUMBERED INSTALLED ALARM INCREASE TRIP POINT DECREASE TRIP POINT DISPLAYS ENGINEERING UNITS AND DECIMAL POS...

Page 30: ...s for the parameter displayed or scroll to EXIT ALRM and press SELECT to access the menus for another alarm if installed or to return to the Main Menu ENTER DEADBAND 15 From the ENTR DB screen press...

Page 31: ...reen s for the parameters displayed or scroll to EXIT ALRM and press SELECT to access the menus for another alarm if installed or to return to the Main Menu SET LATCHING NON LATCHING 27 From the SET L...

Page 32: ...ocked out READ ONLY mode Figure 18 shows the menu 1 From the PASS WORD screen press SELECT to access PASS 2 Use the arrow buttons to increment or decrement the password number to be stored in unit mem...

Page 33: ...ack panel over the top lip of the rail and pivot downward until the housing locks into place To mount the unit on G type rail seat the extrusion under the top lip of the rail and again pivot downward...

Page 34: ...erminal designations VOLTAGE SOURCE 4 WIRE CURRENT SOURCE 2 WIRE CURRENT SOURCE TOP ROW TERMINALS MIDDLE ROW TERMINALS BOTTOM ROW TERMINALS TERMINALS FOR 3PRG AND 4PRG UNITS OR UNITS WITH DPDT RELAYS...

Page 35: ...NO3 NO3 NO2 CM3 CM3 CM2 NC3 NC3 NC2 NO2 CM2 NC2 Relay 1 above Relay 1 above NO4 CM4 NC4 Not Present NO2 CM2 NC2 Relay 2 above 1 Relay 1PRG 2 Relays 2PRG 3 Relays 3PRG 4 Relays 4PRG 1DPDT Relay 2 DPDT...

Page 36: ...Moore Industries instruments can be classified as receivers IPT 2 IPX 2 etc and some can be classified as transmitters TRX TRY etc while some are both a receiver and a transmitter SPA 2 HIM etc Hence...

Page 37: ...LED shows green during normal operation Green indicates that an input sensor or sensors has have been connected and that they are functioning properly TRIP These LEDs one per installed relay show gree...

Page 38: ...into unit memory This can be caused by power loss or fluctuation during power up Reference Junction Compensation Resistor Burnout Internal Table Error The linearization curve pro gramming is not corre...

Page 39: ...THE SOLE AND EXCLUSIVE REM EDIES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRIC...

Reviews: