HarshIO 300 ePN
47
IP67 Digital I/O Modules for PROFINET IO
By default, the HarshIO name displayed is the one defined in the GSD file
molex-harsh300-ip67. You have
to set the name according the HarshIO module name connected to the PROFINET network.
Note: If you don’t know module name or if you are doing the commissioning of the HarshIO module for the
first time, read the section
For the selected HarshIO module, you also have to configure the associated IP address corresponding to the
module name.
The IP address must be unique
.
Fig. E: HarshIO name and IP configuration
Remember! At the PROFINET connection phase between the PLC and the device, the controller sets the IP
address defined in this property box whatever is the IP already stored in the HarshIO device.
Warning! It is highly recommended to define the HarshIO module names and IP addresses before doing
the configuration to ensure a successful commissioning.